Triplen transformer technology (Page 1 of 2)

Third harmonic effects
The third harmonic component of a computer load current is the largest single harmonic component and is typically at least 30% and potentially greater than 80%. Compared to the third, other triplen harmonics may be neglected.

The presence of this harmonic in a distribution system can cause overloading of the neutral cable as well as voltage distortion.

Overloading of the neutral cable
If the percentage of third harmonic in the load is 70%, a not uncommon figure, and the phase currents are 100% then the current in the neutral conductor due to the third harmonic will be:

70% from phase A + 70% from phase B + 70% from phase C

This results in a total neutral current of 210%. As neutral conductors are generally not protected, damage to the neutral conductor will result.

 
UPS Technology
Power Factor Derating
Static Flywheel
Thycon vs ICBT UPS Comparison
Switch Technologies
IGCT Technology
Triplen Transformer Technology
CCR Technology
STS Technology
 
next >>>
   
Copyright © 2006-2008 Thycon Pty Ltd. All rights reserved. Site design by DreamBytes