|
Triplen transformer technology (Page 1 of 2)
Third harmonic effects
The third harmonic component of a computer load current is the largest
single harmonic component and is typically at least 30% and potentially
greater than 80%. Compared to the third, other triplen harmonics may be
neglected.
The presence of this harmonic in a distribution system can cause overloading
of the neutral cable as well as voltage distortion.
Overloading of the neutral cable
If the percentage of third harmonic in the load is 70%, a not uncommon
figure, and the phase currents are 100% then the current in the neutral
conductor due to the third harmonic will be:
• 70%
from phase A + 70% from phase B + 70% from phase C
This results in a total neutral current of 210%. As neutral conductors
are generally not protected, damage to the neutral conductor will result. |