Get in Touch

Triplen Power Distribution Unit

Triplen Power Distribution Unit
The THYCON Triplen Power Distribution Unit (TPDU) is designed to correct any third harmonic content on the current waveform while providing electrical isolation, voltage transformation and extensive monitoring of the load.

Applications

The Triplen PDU is a self-contained power conditioning system that provides reliable computer grade power and single point grounding, while simultaneously trapping system harmonic currents and providing extensive monitoring of the load.

In addition to the elimination of harmonics, the Triplen PDU restores voltage to computer grade quality, provides galvanic isolation between the building power supply and computers and blocks RFI, EMI, common-mode noise and spikes.

The Triplen PDU monitors the 3-phase supply voltage and each of the individual output branch line currents.

A maintenance bypass facility can be provided for the harmonic isolation transformer to allow for maintenance. This maintenance bypass switch is a non-interlocked make before break rotary switch. A soft start facility is provided to limit the transformer and load inrush currents to a maximum of 1.5 times the current rating of the transformer.

Options

The Triplen PDU system components use the MODBUS TCP/IP protocol over Ethernet to communicate requests and parameter passing.
The Triplen PDU is fitted with LEDs indicating Power Available, On-Line and Emergency Shutdown.

The optional Multi Circuit Monitor is a smart LCD panel featuring a simple and effective user interface that incorporates advanced monitoring facilities enabling immediate access to overall input and individual output circuit monitoring.

The Triplen PDU system components use the MODBUS TCP/IP protocol over Ethernet to communicate requests and parameter passing.

Instantaneous values

  • Voltages (L-L and L-N)
  • Line current
  • Real power (1 and 3-phase as appropriate)
  • Apparent power (1 and 3-phase as appropriate)
  • Power factor, including lead/lag indication
  • Voltage distortion (both THD and individual harmonics to the 25th harmonic)
  • Current distortion (both THD and individual harmonics to the 25th harmonic)

Peak demand values

  • Voltages (L-L and L-N)
  • Line current
  • Real power (1 and 3-phase as appropriate)
  • Apparent power (1 and 3-phase as appropriate)

Energy values

  • kWh
  • kVAh

Features & Benefits

24/7 detailed monitoring of individual branch circuits
Treading and load profiling for effective management and planning
Local and remote monitoring
Optimised power utilisation
Optimised availability
3rd harmonic elimination
Single point grounding
High efficiency
High reliability
Low maintenance cost
Compact, modular construction
Australian made

Our Creative Projects